motor overload protection

see NEC standards guide
N.B. - the fuse/circuit breaker are there for short circuit protection, not to protect equipment or people.

prereq information

definitions

FLC

Full-Load Current

service factor

The service factor rating is the amount of output the motor can develop without causing harm to the motor, expressed as a ratio of the rated power.

temperature rise

The temperature rise is the difference of the motor winding temperature when running at its full potential and the ambient temperature.

overload

calculations

  1. Find the motor's FLC

  2. determine Branch circuit conductor current load

    • must be rated to 125% of FLC
    • refer to table 310-16 for temperature ratings
  3. Calculate Branch circuit protection requirements

    • table 430-152 determines the maximum allowable current rating of the fuse or circuit breaker protecting the circuit.
      • This also depends on the type of motor
    • Riveer rules of thumb
      • expect to use only inverse time breakers for loads <30 A
      • or dual element (time-delay) fuses for loads >30 A
  4. Determine the size of the #overload heaters:
    !!!!! Always use the nameplate FLC if given when calculating OVERLOADS !!!!!

    1. the standard overload values are determined by NEC Section 430-32
      if the #service factor 1.15 then use 125% of FLA
      OR if the #temperature rise 40°C then use 125% FLA
      else use 115% of FLA
    2. maximum overload values are found in NEC Section 430-34a:
      if the #service factor 1.15 then use an overload rated 140% of FLA
      OR if the #temperature rise 40°C then use 140% of FLA
      else use an overload rated to 130% of FLA
  5. If you have more than one motor, (or additional loads) on the feeder conductor, then the load calculation is 1.25FLC of the largest motor + of all additional loads

    • When you have more than one motor or you have one motor and an additional load the feeder conductors shall be equal to the sum of the FLC for all the motors and all additional loads plus 25% of the FLC of the largest motor.
      • IMPORTANT: If you have an additional load which is not a motor, and the FLC of the additional load is greater than the largest motor, you do not add 25% to the additional load, you must add the 25% to the largest motor, regardless of the size of the additional load.
      • see an example of how to do this.
  6. feeder protection

    • you can size these down to the next standard size
Powered by Forestry.md