HMI programming
HMI - Human Machine Interface - a little windows PC mounted on a touchscreen
method
- calibrate the touchscreen (optional, required for PanaView Plus Performance)
- don't load an IP address before loading firmware (it will overwrite it anyway.)
- load firmware (PROTIP: load the firmware update on a USB drive; it's easier than downloading it from the internet)
While you're waiting for the firmware to update, connect the PLC and start programming.
After updating the HMI firmware:
PROTIP: use a keyboard for the following steps
- set the password
- next, FactoryTalk View will pop up
- set the IP address of the PLC (see the share drive for a table of standard IP addresses).
- set the time and date
- set the time zone for the delivery location
- exit, enter the default password again to save the settings
- Enable the ping response:
Settings->Ping Response(enter default password to confirm). - Enable VNC:
Settings->VNC on(enter default password to confirm). - Enable VNC control
- enter a password for VNC control
- enter the default password to save the password
- Restart (enter default password to confirm)
- Once the restart is complete, Upload the
RunTime File; The completed program will run on the HMI and define responses to user input.- using the
transfer utilityselect theRunTime Fileyou want, then select the HMI on the ethernet tree as the target. - Once downloaded, the HMI should reboot and load the GUI specified in the
RunTime File.
- using the
models
some of the ones in use at Riveer
PanaView Plus Standard
Slightly cheaper
PanaView Plus Performance
"'performance' means you get less performance"
- You need to calibrate the touchscreen before use with this one.
Logix Edge
- new Rockwell product.
- Runs Factory Talk Optix
- Yocto Linux based mini PC -> 100 x 100 x 53.4 mm
- Max of 35 nodes
- No environmental rating
- does not allow control of motion or safety critical systems.